EXPERIMENTAL
STUDY ON THE PERFORMANCE CHARACTERISTICS OF SCREW REFRIGERATION
COMPRESSOR UNDER PART LOAD CONDITIONS
Wu
Huagen Peng Xueyuan Xing Ziwen
Shu Pengcheng
(School of Energy and Power
Engineering, Xi’an Jiaotong University, Xi’an 710049)
|
|
Abstract: The performance characteristics of twin-screw refrigeration
compressor using various refrigerants under part load conditions are
investigated by experimental research. At first, based on the recorded
p-V indicator diagrams, the various efficiencies of twin-screw
refrigeration compressor under part load conditions are analyzed. Then,
the effects of four kinds of refrigerant, R22, R134a, R404A and R407C,
on compressor performance are presented. As the compressor load falls
down, it is shown that the built-in volume ratio is decreased compared
to that under full load condition and hence the adiabatic efficiency and
adiabatic indicated efficiency of compressor are decreased. However, the
PCO coefficient of performance PCO of refrigeration system is improved.
By comparing the application part load values VAPL of system, R22 is
found to be the best refrigerant with regard to part load operations
among the four refrigerants.
Key
words: Part
load Screw refrigeration compressor Performance characteristics
p-V indicator diagram Refrigerant
CLC No: TH455
Received 20030613, received in revised form
20031130
|