Home|News|Literature|Journal|Instruction|Forum|Member|Introduction

Chinese  Old version

By    In    Search 

  HomeContents of Chinese Journal of Mechanical Engineering 2005 No.11EXPERIMENTAL RESEARCH ON EMPIRICAL MODEL OF FLOW
COEFFICIENT OF ELECTRONIC EXPANSION VALVE
EXPERIMENTAL RESEARCH ON EMPIRICAL MODEL

 OF FLOW COEFFICIENT OF ELECTRONIC
EXPANSION VALVE

 

Zhang Chuan  Ma Shanwei  Chen Jiangping  Chen Zhijiu

(School of Mechanical Engineering, Shanghai Jiaotong University, Shanghai 200030)

 

Abstract: By applying black box theory inlet pressure, inlet subcooling, outlet pressure and valve opening are selected as influence factors to flow coefficient of electronic expansion valve (EEV). The four parameters are performed experimental research and analysis through a special experimental rig of testing flow characters of EEV. Its reducing relative uncertainty of flow coefficient is between 1.97% and 6.28%. Based on the experimental and calculated database, a multiple regression is performed by which an experimental correlation is developed. According to the validity check, the correlation yields the relative deviations range from –7.0% to 6.6%.

Key words: Electronic expansion valve (EEV)  Flow coefficient   Experimental correlation

CLC No: TB663

Received 20040910, received in revised form 20050201

 
Open or Download Full Text of this Paper (PDF File)
 
  About us-Contact us-Site map-Advertisement service-Cooperation-Legal statement  

Address: 22 Baiwanzhuang Dajie, Beijing 100037 China    Tel: 8610-88379907    Fax: 8610-68994557

E-mail: cjme@mail.machineinfo.gov.cn  http: //www.cjmenet.com
©2006 Editorial Office of CJME. All Right Reserved