INDOOR ANALOG
EXPERIMENT AND ENGINEERING APPLICATION ON HIGH TEMPERATURE HEAT PUMP
WANG Zhiguo1, 2 SONG
Yongchen1 LIU Yu1 XIANG Xinyao2 MA Yitai3
(1. School of Energy and Power
Engineering,Dalian University of Technology, Dalian 116024;
2. Qinhuangdao Branch, Daqing Petroleum Institute, Qinhuangdao 066004;
3. Thermal Energy Research
Institute,Tianjin University, Tianjin 300072)
|
|
Abstract: Aiming
at the facts that lots of low temperature waste heat from some
industries(such as oil, chemical, power and steeel works) is abundant
but rarely used, a waste heat recovery analog experiment on a home-made
high temperature heat pump set-up is conducted. According to the test
data and results, the empirical expressions of all performance indexes
are regressed under the condition of using R142b as refrigerant, heat
source temperature at 35~45 °C, heating temperature at 60~85 °C, and
compressor output at 2.3~3.7 kW. Also the impacts of parametric
variations on performance indexes is analyzed. Furthermore, an
engineering trial is performed by an industrial heat pump made overseas
operating in oil field. The investigations indicate massive energy can
be saved if heat pump is applied to recover the low temperature waste
heat from oil production process. The operating cost of heat pump system
is nearly the same as that of heater system, which restricts the
popularization of heat pump.
Key words:High
temperature heat pump Waste heat recovery Analog experiment
Engineering application Performance analysis
CLC No: TB615
国家重点基础研究发展计划(2000026307)和中国博士后科学基金(2005038256)资助项目. Received 20051012, received
in revised form 20060204
|