EXERGY TRANSFER ANALYSIS FOR CENTRIFUGAL
COMPRESSED HIGH POWER HEAT PUMP
DEVICE
XIANG Xinyao CHENG
Qinglin
(Qinhuangdao Branch, Daqing Petroleum
Institute, Qinhuangdao 066004)
|
|
Abstract: According
to exergy transfer theory, establishment of the exergy transfer mode of
unit and device for an online high power centrifugal compressed heat
pump is focused on. Some criterions to analyze and evaluate the devices
and equipments such as exergy exchange rate,
exergy power degressive rate, exergy fluid density degressive rate, and
exergy resistance coefficient are raised and defined. The calculation
formulas for each criterion are presented also. Using these model and
criterions, through an exergy transfer analysis on the energy quality
activities during the process of the energy exchange and transfer in the
heat pump, the results show that
exergy power degressive rate
is the highest in throttle and compressor because the flow speed and
flow state have the instant drastic changes in the process of flow
throttle, which cause the significant loss of exergy, and some
deficiencies exist for the compressor mechanism performance and thermophysical
properties of refrigerants performance. The exergy resistance
coefficient is the highest in evaporator, which reflects that the
structure design has the distinct limitation.
Exergy power degressive rate
and exergy fluid density degressive
rate have the same value in the throttle which indicate that the
structure factors of the equipment and the time conditions have the same
impacts on the throttle. The results of exergy transfer analysis reveal
the influence degree of structure design and thermodynamics property of the main equipment, and thermophysical
properties of refrigerants impact the process of energy usage in
the devices, and indicate the structure design of compressor can be
improved further. The method by flow throttling and intensity of
pressure decreasing is not appropriate in terms of the significant
impacts on the rational energy usage of the devices; the primary problem
of the evaporator is caused by the refrigerant factor but not its
structure design. From the calculation of the energy analysis and exergy
analysis on the devices, it is indicated that energy analysis only
reflects the quantitative energy utilizing, and exergy analysis is only
the static analysis of energy activities. However, in terms of the
dynamic analysis, exergy transfer analysis provides the new information
including not only the design parameters for the heat pump device and
principle equipments, but also the impacts on the performance of energy
usage under the situation with the random running of the equipment
system. Therefore, it can provide the detailed suggestions to improve on
the heat pump unit designs and direct the device operation.
Key words:Centrifugal
compressed Heat pump Exergy transfer
Exergy transfer analysis
CLC No: TK123
国家重点基础研究发展计划资助项目(G2000026307). Received 20050704, received in revised
form 20060223 |